Products of other enterprises
Technical characteristics
- BrandF&F
- Country of manufacturePoland
- Voltage220 V
Description
With a possibility of connection of the external
transformer
of current.
Remark: the RP-614 relay can work with the external transformer of current which primary winding is connected to a priority chain, and measuring contacts of the relay are connected to secondary. The transformer needs to be picked up with such parameters that current of a secondary winding did not exceed 5 A. For example: for connection of the consumer of a priority chain with the maximum current of loading 140 A we use the current transformer with parameters 150/5 A. The coefficient of transformation will make 30:1. In that case, at installation on a scale of the relay of value 2 A, the relay will work at the valid value of current 60 A (2x30=60 A).
Appointment: the relay of current of priority action is intended for control of size of current which is used by electroreceivers and managements of them in a case when their simultaneous work causes an overload of a network of food and operation of safety devices.
Action: value of a threshold of current of consumption in a priority chain at which excess the relay switches off a low-priority electric chain is established by a potentiometer. Decrease in current of consumption in a priority chain gives established to automatic inclusion of a low-priority chain below.
Remark: with the relay of priority action it is necessary to apply automatic safety locks with the reaction time which is not exceeding relay reaction time to electric chains.
Technical characteristics: | |
supply voltage | 220 V, 50 Hz |
current of loading of a low-priority chain | to 16 A |
current of a measuring entrance | 5 A |
operation threshold | 0,5 - 5 A |
power consumption | 0,4 W |
shutdown delay | 0,1 with |
inclusion delay | 0,1 with |
accession of wires | clips screw 2,5 mm2 |
endurance of contacts | 105 inclusions |
range of working temperatures | from -25 °C to +50 °C |
degree of protection | IP40 |
dimensional size | 1 module of S type (17,5 mm) |
installation of the device | on a DIN lath of 35 mm |